Re: PLC Integration with SAP MII

Hi Vivek,

 

  1. The "OPC Server not reachable" is most likely due to either a network issue, or the OPC Server has stopped due to the DataLogger not being licensed; You need to review the Reliable Connection settings for the PCo OPC DA agents. The default is 3 retries and 30 seconds delay per retry. After the retry count is exceeded, the PCo agent goes into Faulted state (red X) and will require a restart to recover; Also need to make sure the OPC Server is running as well and not timed out due to license restriction.
  2. Please provide an export of a PCo Agent Instance log containing the log message at the time the agent instance lost connection with the OPC server and eventually faulted.
  3. I would strongly recommend you disable the Kepware DataLogger plugin if you do not have it licensed. This could also impact the OPC connectivity as well; which would cause the "OPC Server not reachable" errors.
  4. Your PCo and MII, as well as Kepware, are pretty old. Recommend that you consider an upgrade to the latest versions of all products.

 

Regards, Steve